Solar and battery sizer
Enter how much power you use and what must stay on in a power cut. You get a first estimate of panels, batteries and inverter.
Result
About 11.1 kWp of panels, 18 kWh of batteries and a 10 kW inverter.
That keeps 2.5 kW running for 6 hours without the grid, and covers your daytime use while recharging the batteries on a typical day.
Technical detail
A first estimate for budgeting. A real design uses a week of logged load data, local irradiance, roof angle and shading, cable runs and protection.
| Step | Calculation | Result |
|---|---|---|
| Battery, usable | 2.5 kW × 6 h | 15 kWh |
| Battery, nominal | ÷ 0.85 usable depth (LiFePO4) | 17.6 kWh |
| Yield per kWp | 5.2 h × 0.78 performance ratio | 4.06 kWh/day |
| Array | (30.2 daytime + 15 recharge) ÷ 4.06 | 11.1 kWp |
| Inverter | max(load × 1.25, start surge 5.5 kW ÷ 2, array ÷ 1.2) | 10 kW |